Technická data
Název:
SIPLUS S7-1500 F-DI 16x24VDC
Popis:
SIPLUS S7-1500 F-DI 16x24VDC -25 ... +60 DEG C with conformal coating BasedOn: 6ES7526-1BH00-0AB0 . FAILSAFE DIGITAL INPUT MODULE, F-DI 16X24VDC PROFISAFE; 35 MM WIDTH; UP TO PL E (ISO 13849-1)/ SIL3 (IEC 61508)
Technické informace:
General information | ||
Product type designation | F-DI 16x24VDC | |
Firmware version | ||
● FW update possible | Yes | |
Product function | ||
● I&M data | Yes; I&M0 to I&M3 | |
Operating mode | ||
● DI | Yes | |
Supply voltage | ||
Rated value (DC) | 24 V | |
permissible range, lower limit (DC) | 19.2 V | |
permissible range, upper limit (DC) | 28.8 V | |
Reverse polarity protection | Yes | |
Input current | ||
Current consumption (rated value) | 50 mA | |
Encoder supply | ||
Number of outputs | 4 | |
Short-circuit protection | Yes; Electronic (response threshold 0.7 A to 1.8 A) | |
24 V encoder supply | ||
● 24 V | Yes; min. L+ (-1.5 V) | |
● Short-circuit protection | Yes | |
● Output current, max. | 300 mA; Max. 100 mA when mounted vertically | |
Power | ||
Power available from the backplane bus | 0.9 W | |
Power loss | ||
Power loss, typ. | 4.6 W | |
Address area | ||
Address space per module | ||
● Address space per module, max. | 9 byte | |
Hardware configuration | ||
Automatic encoding | Yes | |
● Electronic coding element type F | Yes | |
Digital inputs | ||
Number of digital inputs | 16 | |
Source/sink input | Yes; P-reading | |
Input characteristic curve in accordance with IEC 61131, type 1 | Yes | |
Input voltage | ||
● Type of input voltage | DC | |
● Rated value (DC) | 24 V | |
● for signal "0" | -30 to +5V | |
● for signal "1" | +15 to +30V | |
Input current | ||
● for signal "1", typ. | 3.7 mA | |
Input delay (for rated value of input voltage) | ||
for standard inputs | ||
— parameterizable | Yes | |
— at "0" to "1", min. | 0.4 ms | |
— at "0" to "1", max. | 20 ms | |
— at "1" to "0", min. | 0.4 ms | |
— at "1" to "0", max. | 20 ms | |
Cable length | ||
● shielded, max. | 1 000 m | |
● unshielded, max. | 500 m | |
Interrupts/diagnostics/status information | ||
Diagnostics function | Yes | |
Alarms | ||
● Diagnostic alarm | Yes | |
● Hardware interrupt | No | |
Diagnostic messages | ||
● Monitoring the supply voltage | Yes | |
● Wire-break | No | |
● Short-circuit | Yes | |
● Group error | Yes | |
Diagnostics indication LED | ||
● RUN LED | Yes; Green LED | |
● ERROR LED | Yes; Red LED | |
● Channel status display | Yes; Green LED | |
● for channel diagnostics | Yes; Red LED | |
● for module diagnostics | Yes; Red LED | |
Potential separation | ||
Potential separation channels | ||
● between the channels and backplane bus | Yes | |
Permissible potential difference | ||
between different circuits | 75 V DC/60 V AC (base isolation) | |
Isolation | ||
Isolation tested with | 707 V DC (type test) | |
Ambient conditions | ||
Ambient temperature during operation | ||
● horizontal installation, min. | -25 °C; = Tmin | |
● horizontal installation, max. | 60 °C; = Tmax | |
Relative humidity | ||
● With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | |
Dimensions | ||
Width | 35 mm | |
Height | 147 mm | |
Depth | 129 mm | |
Weights | ||
Weight, approx. | 280 g | |
last modified: | 09/25/2017 |