Technická data
Název:
SIPLUS S7-1500 AI 8XU/R/RTD/TC HF
Popis:
SIPLUS S7-1500 AI 8XU/R/RTD/TC HF 0 ... +60 °C with conformal coating BasedOn: 6ES7531-7PF00-0AB0 . Analog Input Module AI 8 X U/R/RTD/TC HF, 16 Bits of Resolution, Accuracy 0.1%, 8 Channels in groups of 1; common mode Voltage: 30V AC/60V DC, Diagnosis, Processalarms; incl. infeed element, Shield clamp and Shield terminal
Technické informace:
General information | ||
Product type designation | AI 8xU/R/RTD/TC HF | |
Firmware version | ||
● FW update possible | Yes | |
Product function | ||
● I&M data | Yes; I&M0 to I&M3 | |
● Measuring range scalable | Yes | |
● Scalable measured values | No | |
● Adjustment of measuring range | No | |
Engineering with | ||
● PROFIBUS as of GSD version/GSD revision | V1.0 / V5.1 | |
● PROFINET as of GSD version/GSD revision | V2.3 / - | |
Operating mode | ||
● Oversampling | No | |
● MSI | Yes | |
CiR – Configuration in RUN | ||
Reparameterization possible in RUN | Yes | |
Calibration possible in RUN | Yes | |
Supply voltage | ||
Rated value (DC) | 24 V | |
permissible range, lower limit (DC) | 20.4 V | |
permissible range, upper limit (DC) | 28.8 V | |
Reverse polarity protection | Yes | |
Input current | ||
Current consumption, max. | 55 mA; with 24 V DC supply | |
Power | ||
Power available from the backplane bus | 0.85 W | |
Power loss | ||
Power loss, typ. | 1.9 W | |
Analog inputs | ||
Number of analog inputs | 8; Plus one additional RTD (reference) channel | |
● For voltage measurement | 8; Plus one additional RTD (reference) channel | |
● For resistance/resistance thermometer measurement | 8; Plus one additional RTD (reference) channel | |
● For thermocouple measurement | 8; Plus one additional RTD (reference) channel | |
permissible input voltage for voltage input (destruction limit), max. | 20 V | |
Technical unit for temperature measurement adjustable | Yes; °C/°F/K | |
Input ranges (rated values), voltages | ||
● 0 to +5 V | No | |
● 0 to +10 V | No | |
● 1 V to 5 V | No | |
● -1 V to +1 V | Yes | |
● Input resistance (-1 V to +1 V) | 10 MΩ | |
● -10 V to +10 V | No | |
● -2.5 V to +2.5 V | No | |
● -25 mV to +25 mV | Yes | |
● Input resistance (-25 mV to +25 mV) | 10 MΩ | |
● -250 mV to +250 mV | Yes | |
● Input resistance (-250 mV to +250 mV) | 10 MΩ | |
● -5 V to +5 V | No | |
● -50 mV to +50 mV | Yes | |
● Input resistance (-50 mV to +50 mV) | 10 MΩ | |
● -500 mV to +500 mV | Yes | |
● Input resistance (-500 mV to +500 mV) | 10 MΩ | |
● -80 mV to +80 mV | Yes | |
● Input resistance (-80 mV to +80 mV) | 10 MΩ | |
Input ranges (rated values), currents | ||
● 0 to 20 mA | No | |
● -20 mA to +20 mA | No | |
● 4 mA to 20 mA | No | |
Input ranges (rated values), thermocouples | ||
● Type B | Yes | |
● Input resistance (Type B) | 10 MΩ | |
● Type C | Yes | |
● Input resistance (Type C) | 10 MΩ | |
● Type E | Yes | |
● Input resistance (Type E) | 10 MΩ | |
● Type J | Yes | |
● Input resistance (type J) | 10 MΩ | |
● Type K | Yes | |
● Input resistance (Type K) | 10 MΩ | |
● Type L | No | |
● Type N | Yes | |
● Input resistance (Type N) | 10 MΩ | |
● Type R | Yes | |
● Input resistance (Type R) | 10 MΩ | |
● Type S | Yes | |
● Input resistance (Type S) | 10 MΩ | |
● Type T | Yes | |
● Input resistance (Type T) | 10 MΩ | |
● Type TXK/TXK(L) to GOST | Yes | |
● Input resistance (Type TXK/TXK(L) to GOST) | 10 MΩ | |
Input ranges (rated values), resistance thermometer | ||
● Cu 10 | Yes; Standard/climate | |
● Input resistance (Cu 10) | 10 MΩ | |
● Cu 10 according to GOST | Yes; Standard/climate | |
● Input resistance (Cu 10 according to GOST) | 10 MΩ | |
● Cu 50 | Yes; Standard/climate | |
● Input resistance (Cu 50) | 10 MΩ | |
● Cu 50 according to GOST | Yes; Standard/climate | |
● Input resistance (Cu 50 according to GOST) | 10 MΩ | |
● Cu 100 | Yes; Standard/climate | |
● Input resistance (Cu 100) | 10 MΩ | |
● Cu 100 according to GOST | Yes; Standard/climate | |
● Input resistance (Cu 100 according to GOST) | 10 MΩ | |
● Ni 10 | Yes; Standard/climate | |
● Input resistance (Ni 10) | 10 MΩ | |
● Ni 10 according to GOST | Yes; Standard/climate | |
● Input resistance (Ni 10 according to GOST) | 10 MΩ | |
● Ni 100 | Yes; Standard/climate | |
● Input resistance (Ni 100) | 10 MΩ | |
● Ni 100 according to GOST | Yes; Standard/climate | |
● Input resistance (Ni 100 according to GOST) | 10 MΩ | |
● Ni 1000 | Yes; Standard/climate | |
● Input resistance (Ni 1000) | 10 MΩ | |
● Ni 1000 according to GOST | Yes; Standard/climate | |
● Input resistance (Ni 1000 according to GOST) | 10 MΩ | |
● LG-Ni 1000 | Yes; Standard/climate | |
● Input resistance (LG-Ni 1000) | 10 MΩ | |
● Ni 120 | Yes; Standard/climate | |
● Input resistance (Ni 120) | 10 MΩ | |
● Ni 120 according to GOST | Yes; Standard/climate | |
● Input resistance (Ni 120 according to GOST) | 10 MΩ | |
● Ni 200 | Yes; Standard/climate | |
● Input resistance (Ni 200) | 10 MΩ | |
● Ni 200 according to GOST | Yes; Standard/climate | |
● Input resistance (Ni 200 according to GOST) | 10 MΩ | |
● Ni 500 | Yes; Standard/climate | |
● Input resistance (Ni 500) | 10 MΩ | |
● Ni 500 according to GOST | Yes; Standard/climate | |
● Input resistance (Ni 500 according to GOST) | 10 MΩ | |
● Pt 10 | Yes; Standard/climate | |
● Input resistance (Pt 10) | 10 MΩ | |
● Pt 10 according to GOST | Yes; Standard/climate | |
● Input resistance (Pt 10 according to GOST) | 10 MΩ | |
● Pt 50 | Yes; Standard/climate | |
● Input resistance (Pt 50) | 10 MΩ | |
● Pt 50 according to GOST | Yes; Standard/climate | |
● Input resistance (Pt 50 according to GOST) | 10 MΩ | |
● Pt 100 | Yes; Standard/climate | |
● Input resistance (Pt 100) | 10 MΩ | |
● Pt 100 according to GOST | Yes; Standard/climate | |
● Input resistance (Pt 100 according to GOST) | 10 MΩ | |
● Pt 1000 | Yes; Standard/climate | |
● Input resistance (Pt 1000) | 10 MΩ | |
● Pt 1000 according to GOST | Yes; Standard/climate | |
● Input resistance (Pt 1000 according to GOST) | 10 MΩ | |
● Pt 200 | Yes; Standard/climate | |
● Input resistance (Pt 200) | 10 MΩ | |
● Pt 200 according to GOST | Yes; Standard/climate | |
● Input resistance (Pt 200 according to GOST) | 10 MΩ | |
● Pt 500 | Yes; Standard/climate | |
● Input resistance (Pt 500) | 10 MΩ | |
● Pt 500 according to GOST | Yes; Standard/climate | |
● Input resistance (Pt 500 according to GOST) | 10 MΩ | |
Input ranges (rated values), resistors | ||
● 0 to 150 ohms | Yes | |
● Input resistance (0 to 150 ohms) | 10 MΩ | |
● 0 to 300 ohms | Yes | |
● Input resistance (0 to 300 ohms) | 10 MΩ | |
● 0 to 600 ohms | Yes | |
● Input resistance (0 to 600 ohms) | 10 MΩ | |
● 0 to 3000 ohms | No | |
● 0 to 6000 ohms | Yes | |
● Input resistance (0 to 6000 ohms) | 10 MΩ | |
● PTC | Yes | |
● Input resistance (PTC) | 10 MΩ | |
Thermocouple (TC) | ||
Temperature compensation | ||
— parameterizable | Yes | |
— internal temperature compensation | Yes | |
— external temperature compensation via RTD | Yes | |
— Compensation for 0 °C reference point temperature | Yes; fixed value can be set | |
— Reference channel of the module | Yes; 9th channel that can be used as a genuine 9th RTD channel regardless of the parameterization of the other channels, or that can be used for compensation in the case of TC measurement | |
Cable length | ||
● shielded, max. | 800 m; at U; 200 m at R/RTD/TC | |
Analog value generation for the inputs | ||
Integration and conversion time/resolution per channel | ||
● Resolution with overrange (bit including sign), max. | 16 bit | |
● Integration time, parameterizable | Yes | |
● Integration time (ms) | Fast mode: 2.5 / 16.67 / 20 / 100 ms, standard mode: 7.5 / 50 / 60 / 300 ms | |
● Basic conversion time, including integration time (ms) | Fast mode: 4 / 18 / 22 / 102 ms; Standard mode: 9 / 52 / 62 / 302 ms | |
— additional conversion time for wire-break monitoring | Thermocouples, 150 Ohm, 300 Ohm, 600 Ohm, Cu10, Cu50, Cu100, Ni10, Ni50, Ni100, Ni120, Ni200, Pt10, Pt50, Pt100, Pt200: 4 ms; 6 kOhm, Ni500, Ni1000, LG-Ni1000, Pt500, Pt1000: 13 ms | |
● Interference voltage suppression for interference frequency f1 in Hz | 400 / 60 / 50 / 10 Hz | |
● Basic execution time of the module (all channels released) | Corresponds to the channel with the highest basic conversion time | |
Smoothing of measured values | ||
● parameterizable | Yes | |
● Step: None | Yes | |
● Step: low | Yes | |
● Step: Medium | Yes | |
● Step: High | Yes | |
Encoder | ||
Connection of signal encoders | ||
● for voltage measurement | Yes | |
● for current measurement as 2-wire transducer | No | |
● for current measurement as 4-wire transducer | No | |
● for resistance measurement with two-wire connection | Yes | |
● for resistance measurement with three-wire connection | Yes; All measuring ranges except PTC; internal compensation of the cable resistances | |
● for resistance measurement with four-wire connection | Yes; All measuring ranges except PTC | |
Errors/accuracies | ||
Linearity error (relative to input range), (+/-) | 0.02 % | |
Temperature error (relative to input range), (+/-) | 0.005 %/K | |
Crosstalk between the inputs, max. | -80 dB | |
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) | 0.02 % | |
Temperature error of internal compensation | ±1,5 °C | |
Operational error limit in overall temperature range | ||
● Voltage, relative to input range, (+/-) | 0.1 % | |
● Resistance, relative to input range, (+/-) | 0.1 % | |
● Resistance thermometer, relative to input range, (+/-) | Cuxxx Standard: ±0.5 K, Cuxxx Klima: ±0.5 K, Ptxxx Standard: ±1 K, Ptxxx Klima: ±0.5 K, Nixxx Standard: ±0.5 K, Nixxx Klima: ±0.3 K | |
● Thermocouple, relative to input range, (+/-) | Type B: > 600 °C ±2 K, Type E: > -200 °C ±1 K, Type J: > -210 °C ±1 K, Type K: > -200 °C ±2 K, Type N: > -200 °C ±2 K, Type R: > 0 °C ±2 K, Type S: > 0 °C ±2 K, Type T: > -200 °C ±1 K, Type C: ±4 K, Type TXK/TXK(L): ±1 K | |
Basic error limit (operational limit at 25 °C) | ||
● Voltage, relative to input range, (+/-) | 0.05 % | |
● Resistance, relative to input range, (+/-) | 0.05 % | |
● Resistance thermometer, relative to input range, (+/-) | Cuxxx Standard: ±0.3 K, Cuxxx Klima: ±0.2 K, Ptxxx Standard: ±0.5 K, Ptxxx Klima: ±0.2 K, Nixxx Standard: ±0.3 K, Nixxx Klima: ±0.15 K | |
● Thermocouple, relative to input range, (+/-) | Type B: > 600 °C ±1 K, Type E: > -200 °C ±0.5 K, Type J: > -210 °C ±0.5 K, Type K: > -200 °C ±1 K, Type N: > -200 °C ±1 K, Type R: > 0 °C ±1 K, Type S: > 0 °C ±1 K, Type T: > -200 °C ±0.5 K, Type C: ±2 K, Type TXK/TXK(L): ±0.5 K | |
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency | ||
● Series mode interference (peak value of interference < rated value of input range), min. | 80 dB; in the Standard operating mode, 40 dB in the Fast operating mode | |
● Common mode voltage, max. | 60 V DC/30 V AC | |
● Common mode interference, min. | 80 dB | |
Isochronous mode | ||
Isochronous operation (application synchronized up to terminal) | No | |
Interrupts/diagnostics/status information | ||
Diagnostics function | Yes | |
Alarms | ||
● Diagnostic alarm | Yes | |
● Limit value alarm | Yes; two upper and two lower limit values in each case | |
Diagnostic messages | ||
● Monitoring the supply voltage | Yes | |
● Wire-break | Yes; Only with TC, R, RTD | |
● Overflow/underflow | Yes | |
Diagnostics indication LED | ||
● RUN LED | Yes; Green LED | |
● ERROR LED | Yes; Red LED | |
● Monitoring of the supply voltage (PWR-LED) | Yes; Green LED | |
● Channel status display | Yes; Green LED | |
● for channel diagnostics | Yes; Red LED | |
● for module diagnostics | Yes; Red LED | |
Potential separation | ||
Potential separation channels | ||
● between the channels | Yes | |
● between the channels, in groups of | 1 | |
● between the channels and backplane bus | Yes | |
● between the channels and the power supply of the electronics | Yes | |
Isolation | ||
Isolation tested with | 2 000 V DC between the channels and the supply voltage L+; 2 000 V DC between the channels and the backplane bus; 2 000 V DC between the channels; 707 V DC (type test) between the supply voltage L+ and the backplane bus | |
Ambient conditions | ||
Ambient temperature during operation | ||
● horizontal installation, min. | 0 °C | |
● horizontal installation, max. | 60 °C | |
● vertical installation, min. | 0 °C | |
● vertical installation, max. | 40 °C | |
Relative humidity | ||
● With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation | |
Decentralized operation | ||
Prioritized startup | Yes | |
Dimensions | ||
Width | 35 mm | |
Height | 147 mm | |
Depth | 129 mm | |
Weights | ||
Weight, approx. | 290 g | |
Other | ||
Note: | For the R/RDT three-wire measurement, the conductor compensation is made alternating with the measurement. This then requires two module cycles for a measured value. | |
last modified: | 09/25/2017 |