Technická data
Název:
SIPLUS S7-1500 TM COUNT 2X24V
Popis:
SIPLUS S7-1500 TM COUNT 2X24V -40 ... +70 DEGREES C WITH CONFORMAL COATING BASED ON 6ES7550-1AA00-0AB0 . COUNTING MODULE, 2 CHANNELS FOR 24V INCREMENTAL ENCODER OR 24V PULSES, 3DI, 2DQ PER CHANNEL
Technické informace:
General information | ||
Product type designation | TM Count 2x24V | |
Product function | ||
● I&M data | Yes | |
Installation type/mounting | ||
Rail mounting possible | Yes; S7-1500 mounting rail | |
Supply voltage | ||
Load voltage L+ | ||
● Rated value (DC) | 24 V | |
● permissible range, lower limit (DC) | 19.2 V | |
● permissible range, upper limit (DC) | 28.8 V | |
● Reverse polarity protection | Yes | |
Input current | ||
Current consumption, max. | 75 mA; without load | |
Encoder supply | ||
Number of outputs | 1; A common 24V encoder supply for both channels | |
24 V encoder supply | ||
● 24 V | Yes; L+ (-0.8 V) | |
● Short-circuit protection | Yes | |
● Output current, max. | 1 A; Total current of all encoders / channels; > +60 °C max. total current 0.5 A | |
Power | ||
Power available from the backplane bus | 1.3 W | |
Power loss | ||
Power loss, typ. | 4 W | |
Address area | ||
Occupied address area | ||
● Inputs | 16 byte; Per channel | |
● Outputs | 12 byte; per channel; 4 bytes for Motion Control | |
Digital inputs | ||
Number of digital inputs | 6; 3 per channel | |
Digital inputs, parameterizable | Yes | |
Input characteristic curve in accordance with IEC 61131, type 3 | Yes | |
Digital input functions, parameterizable | ||
● Gate start/stop | Yes | |
● Capture | Yes | |
● Synchronization | Yes | |
● Freely usable digital input | Yes | |
Input voltage | ||
● Rated value (DC) | 24 V | |
● for signal "0" | -30 to +5V | |
● for signal "1" | +11 to +30V | |
● permissible voltage at input, min. | -30 V | |
● permissible voltage at input, max. | 30 V | |
Input current | ||
● for signal "1", typ. | 2.5 mA | |
Input delay (for rated value of input voltage) | ||
for standard inputs | ||
— parameterizable | Yes; none / 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms | |
— at "0" to "1", min. | 6 µs; for parameterization "none" | |
— at "1" to "0", min. | 6 µs; for parameterization "none" | |
for counter/technological functions | ||
— parameterizable | Yes | |
Cable length | ||
● shielded, max. | 1 000 m | |
● unshielded, max. | 600 m | |
Digital outputs | ||
Type of digital output | Transistor | |
Number of digital outputs | 4; 2 per channel | |
Digital outputs, parameterizable | Yes | |
Short-circuit protection | ||
● Response threshold, typ. | 1 A | |
Limitation of inductive shutdown voltage to | L+ (-33 V) | |
Controlling a digital input | Yes | |
Digital output functions, parameterizable | ||
● Switching tripped by comparison values | Yes | |
● Freely usable digital output | Yes | |
Switching capacity of the outputs | ||
● with resistive load, max. | 0.5 A; Per digital output | |
● on lamp load, max. | 5 W | |
Load resistance range | ||
● lower limit | 48 Ω | |
● upper limit | 12 kΩ | |
Output voltage | ||
● for signal "1", min. | 23.2 V; L+ (-0.8 V) | |
Output current | ||
● for signal "1" rated value | 0.5 A; Per digital output | |
● for signal "1" permissible range, max. | 0.6 A; Per digital output | |
● for signal "1" minimum load current | 2 mA | |
● for signal "0" residual current, max. | 0.5 mA | |
Output delay with resistive load | ||
● "0" to "1", max. | 50 µs | |
● "1" to "0", max. | 50 µs | |
Switching frequency | ||
● with resistive load, max. | 10 kHz | |
● with inductive load, max. | 0.5 Hz; Acc. to IEC 60947-5-1, DC-13; observe derating curve | |
● on lamp load, max. | 10 Hz | |
Total current of the outputs | ||
● Current per module, max. | 2 A; > +60 °C max. total current of outputs 1 A | |
Cable length | ||
● shielded, max. | 1 000 m | |
● unshielded, max. | 600 m | |
Encoder | ||
Connectable encoders | ||
● 2-wire sensor | Yes | |
— permissible quiescent current (2-wire sensor), max. | 1.5 mA | |
Encoder signals, incremental encoder (asymmetrical) | ||
● Input voltage | 24 V | |
● Input frequency, max. | 200 kHz | |
● Counting frequency, max. | 800 kHz; with quadruple evaluation | |
● Cable length, shielded, max. | 600 m; depending on input frequency, encoder and cable quality; max. 50 m at 200 kHz | |
● Signal filter, parameterizable | Yes | |
● Incremental encoder with A/B tracks, 90° phase offset | Yes | |
● Incremental encoder with A/B tracks, 90° phase offset and zero track | Yes | |
● Pulse encoder | Yes | |
● Pulse encoder with direction | Yes | |
● Pulse encoder with one impulse signal per count direction | Yes | |
Encoder signal 24 V | ||
— permissible voltage at input, min. | -30 V | |
— permissible voltage at input, max. | 30 V | |
Interface types | ||
● Input characteristic curve in accordance with IEC 61131, type 3 | Yes | |
● Source/sink input | Yes | |
Isochronous mode | ||
Isochronous operation (application synchronized up to terminal) | Yes | |
Filtering and processing time (TCI), min. | 130 µs | |
Bus cycle time (TDP), min. | 250 µs | |
Interrupts/diagnostics/status information | ||
Alarms | ||
● Diagnostic alarm | Yes | |
● Hardware interrupt | Yes | |
Diagnostic messages | ||
● Monitoring the supply voltage | Yes | |
● Wire-break | Yes | |
● Short-circuit | Yes | |
● A/B transition error at incremental encoder | Yes | |
Diagnostics indication LED | ||
● RUN LED | Yes; Green LED | |
● ERROR LED | Yes; Red LED | |
● MAINT LED | Yes; yellow LED | |
● Monitoring of the supply voltage (PWR-LED) | Yes; Green LED | |
● Channel status display | Yes; Green LED | |
● for channel diagnostics | Yes; Red LED | |
● Status indicator backward counting (green) | Yes | |
● Status indicator forward counting (green) | Yes | |
Integrated Functions | ||
Number of counters | 2 | |
Counting frequency (counter) max. | 800 kHz; with quadruple evaluation | |
Counting functions | ||
● Can be used with TO High_Speed_Counter | Yes | |
● Continuous counting | Yes | |
● Counter response parameterizable | Yes | |
● Hardware gate via digital input | Yes | |
● Software gate | Yes | |
● Event-controlled stop | Yes | |
● Synchronization via digital input | Yes | |
● Counting range, parameterizable | Yes | |
Comparator | ||
— Number of comparators | 2; Per channel | |
— Direction dependency | Yes | |
— Can be changed from user program | Yes | |
Position detection | ||
● Suitable for S7-1500 Motion Control | Yes | |
Measuring functions | ||
● Measuring time, parameterizable | Yes | |
● Dynamic measurement period adjustment | Yes | |
● Number of thresholds, parameterizable | 2 | |
Measuring range | ||
— Frequency measurement, min. | 0.04 Hz | |
— Frequency measurement, max. | 800 kHz | |
— Cycle duration measurement, min. | 1.25 µs | |
— Cycle duration measurement, max. | 25 s | |
Accuracy | ||
— Frequency measurement | 100 ppm; depending on measuring interval and signal evaluation | |
— Cycle duration measurement | 100 ppm; depending on measuring interval and signal evaluation | |
— Velocity measurement | 100 ppm; depending on measuring interval and signal evaluation | |
Potential separation | ||
Potential separation channels | ||
● between the channels | No | |
● between the channels and backplane bus | Yes | |
● Between the channels and load voltage L+ | No | |
Permissible potential difference | ||
between different circuits | 75 V DC/60 V AC (base isolation) | |
Isolation | ||
Isolation tested with | 707 V DC (type test) | |
Ambient conditions | ||
Ambient temperature during operation | ||
● horizontal installation, min. | -40 °C; = Tmin; Startup @ -25 °C | |
● horizontal installation, max. | 70 °C; = Tmax; note derating for inductive loads; > +60 °C total current of the encoder supply max. 0.5 A, total current of the outputs max. 1 A | |
● vertical installation, min. | -40 °C; = Tmin; Startup @ -25 °C | |
● vertical installation, max. | 40 °C; Please note derating for inductive loads | |
Extended ambient conditions | ||
● relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | |
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Decentralized operation | ||
to SIMATIC S7-1500 | Yes | |
to standard PROFINET controller | Yes | |
Dimensions | ||
Width | 35 mm | |
Height | 147 mm | |
Depth | 129 mm | |
Weights | ||
Weight, approx. | 250 g | |
last modified: | 02/01/2017 |