Technická data
Název:
SIPLUS S7-1500 DI 32X24VDC HF
Popis:
SIPLUS S7-1500 DI 32X24VDC HF -40 ... +70 DEGREES C WITH CONFORMAL COATING BASED ON 6ES7521-1BL00-0AB0 . DIGITAL OUTPUT MODULE DQ 16 X 24VDC/0.5A; 16 CHANNELS IN GROUPS OF 8, 4 A PER GROUP; DIAGNOSIS; SUBSTITUTE VALUE
Technické informace:
General information | ||
Product type designation | DI 32x24VDC HF | |
HW functional status | E01 | |
Firmware version | V1.0.0 | |
Product function | ||
● I&M data | Yes; I&M0 to I&M3 | |
Engineering with | ||
● STEP 7 TIA Portal configurable/integrated as of version | V12 / V12 | |
● STEP 7 configurable/integrated as of version | V5.5 SP3 / - | |
Supply voltage | ||
Rated value (DC) | 24 V | |
permissible range, lower limit (DC) | 19.2 V | |
permissible range, upper limit (DC) | 28.8 V | |
Reverse polarity protection | Yes | |
Input current | ||
Current consumption, max. | 40 mA; 20 mA per group with 24 V DC supply | |
Power | ||
Power available from the backplane bus | 1.1 W | |
Power loss | ||
Power loss, typ. | 4.2 W | |
Digital inputs | ||
Number of digital inputs | 32; > +60 °C, number of simultaneously controllable inputs max. 16 | |
Source/sink input | P-reading | |
Input characteristic curve in accordance with IEC 61131, type 3 | Yes | |
Input voltage | ||
● Type of input voltage | DC | |
● Rated value (DC) | 24 V | |
● for signal "0" | -30 to +5V | |
● for signal "1" | +11 to +30V | |
Input current | ||
● for signal "1", typ. | 2.5 mA | |
Input delay (for rated value of input voltage) | ||
for standard inputs | ||
— parameterizable | Yes; 0.05 / 0.1 / 0.4 / 1.6 / 3.2 / 12.8 / 20 ms | |
— at "0" to "1", min. | 0.05 ms | |
— at "0" to "1", max. | 20 ms | |
— at "1" to "0", min. | 0.05 ms | |
— at "1" to "0", max. | 20 ms | |
for interrupt inputs | ||
— parameterizable | Yes | |
Cable length | ||
● shielded, max. | 1 000 m | |
● unshielded, max. | 600 m | |
Encoder | ||
Connectable encoders | ||
● 2-wire sensor | Yes | |
— permissible quiescent current (2-wire sensor), max. | 1.5 mA | |
Isochronous mode | ||
Isochronous operation (application synchronized up to terminal) | Yes | |
Filtering and processing time (TCI), min. | 80 µs; At 50 μs filter time | |
Bus cycle time (TDP), min. | 250 µs | |
Interrupts/diagnostics/status information | ||
Diagnostics function | Yes | |
Alarms | ||
● Diagnostic alarm | Yes | |
● Hardware interrupt | Yes | |
Diagnostic messages | ||
● Monitoring the supply voltage | Yes | |
● Wire-break | Yes; to I < 350 µA | |
● Short-circuit | No | |
● Fuse blown | No | |
Diagnostics indication LED | ||
● RUN LED | Yes; Green LED | |
● ERROR LED | Yes; Red LED | |
● Monitoring of the supply voltage (PWR-LED) | Yes; Green LED | |
● Channel status display | Yes; Green LED | |
● for channel diagnostics | Yes; Red LED | |
● for module diagnostics | Yes; Red LED | |
Potential separation | ||
Potential separation channels | ||
● between the channels | Yes | |
● between the channels, in groups of | 16 | |
● between the channels and backplane bus | Yes | |
● between the channels and the power supply of the electronics | No | |
Permissible potential difference | ||
between different circuits | 75 V DC/60 V AC (base isolation) | |
Isolation | ||
Isolation tested with | 707 V DC (type test) | |
Ambient conditions | ||
Ambient temperature during operation | ||
● horizontal installation, min. | -40 °C; = Tmin | |
● horizontal installation, max. | 70 °C; = Tmax; > +60 °C number of simultaneously controllable inputs max. 16 | |
● vertical installation, min. | -40 °C; = Tmin | |
● vertical installation, max. | 40 °C; = Tmax | |
Extended ambient conditions | ||
● relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | |
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Decentralized operation | ||
Fast Startup supported | Yes; 500 ms | |
Dimensions | ||
Width | 35 mm | |
Height | 147 mm | |
Depth | 129 mm | |
Weights | ||
Weight, approx. | 260 g | |
last modified: | 02/01/2017 |