Technická data
Název:
SIPLUS S7-1500 PS 25W 24V DC
Popis:
SIPLUS S7-1500 PS 1505 25W 24VD -25 ... +70 DEGEEES C WITH CONFORMAL COATING BASED ON 6ES7505-0KA00-0AB0 . SYSTEM POWER SUPPLY SUPPLIES THE OPERATING VOLTAGE THE S7-1500 VIA THE BACKPLANE B
Technické informace:
General information | ||
Product type designation | PS 25W 24VDC | |
HW functional status | E01 | |
Firmware version | V1.0.0 | |
Engineering with | ||
● STEP 7 TIA Portal configurable/integrated as of version | V12 / V12 | |
● STEP 7 configurable/integrated as of version | V5.5 SP3 or higher | |
Redundancy | ||
● Redundancy capability | Yes | |
— for uprating | Yes | |
Supply voltage | ||
Rated value (DC) | 24 V; SELV | |
permissible range, lower limit (DC) | Static 19.2 V, dynamic 18.5 V | |
permissible range, upper limit (DC) | Static 28.8 V, dynamic 30.2 V | |
Reverse polarity protection | Yes | |
Short-circuit protection | Yes | |
Mains buffering | ||
● Mains/voltage failure stored energy time | 20 ms | |
Output current | ||
Short-circuit protection | Yes | |
Power | ||
Infeed power to the backplane bus | 25 W; > +60 °C max. power input 12.5 W | |
Power loss | ||
Power loss at nominal rating conditions | 6.2 W | |
Interrupts/diagnostics/status information | ||
Status indicator | Yes | |
Potential separation | ||
primary/secondary | Yes; Electrical isolation for max. 60 V AC/75 V DC (base isolation) | |
Isolation | ||
Isolation tested with | 707 V DC (type test) | |
EMC | ||
Interference immunity against voltage surge | ||
● on the supply lines acc. to IEC 61000-4-5 | Yes; +/- 1 kV (acc. to IEC 61000-4-5; 1995; surge symm.), +/- 2 kV (acc. to IEC 61000-4-5; 1995; surge asymm.), no external protective circuit required | |
Degree and class of protection | ||
Degree of protection acc. to EN 60529 | IP20 | |
Protection class | 3; with protective conductor | |
Ambient conditions | ||
Ambient temperature during operation | ||
● min. | -40 °C; = Tmin; Startup @ -25 °C | |
● max. | 70 °C; = Tmax; for vertical mounting position Tmax = +40 °C | |
Extended ambient conditions | ||
● relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | |
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Dimensions | ||
Width | 35 mm | |
Height | 147 mm | |
Depth | 129 mm | |
Weights | ||
Weight, approx. | 350 g | |
last modified: | 02/01/2017 |