SIPLUS S7-400 SM432 8AAFOR MEDIAL STRESSBASED ON 6ES7432-1HF00-0AB0
Technická data
Název:
SIPLUS_SM432_8AA
Popis:
SIPLUS S7-400 SM432 8AA FOR MEDIAL STRESS BASED ON 6ES7432-1HF00-0AB0
Technické informace:
SIPLUS S7-400 SM432 8AA FOR MEDIAL STRESS BASED ON 6ES7432-1HF00-0AB0
Supply voltage
Load voltage L+
● Rated value (DC)
24 V
● Reverse polarity protection
Yes
Input current
from supply voltage L+, max.
400 mA
from backplane bus 5 V DC, max.
150 mA
Power loss
Power loss, typ.
9 W
Analog outputs
Number of analog outputs
8
Voltage output, short-circuit protection
Yes
Voltage output, short-circuit current, max.
30 mA
Current output, no-load voltage, max.
19 V
Output ranges, voltage
● 0 to 10 V
Yes
● 1 V to 5 V
Yes
● -10 V to +10 V
Yes
Output ranges, current
● 0 to 20 mA
Yes
● -20 mA to +20 mA
Yes
● 4 mA to 20 mA
Yes
Load impedance (in rated range of output)
● with voltage outputs, min.
1 kΩ
● with voltage outputs, capacitive load, max.
1 µF
● with current outputs, max.
500 Ω; 600 ohms if common-mode-voltage reduced to <1 V
Cable length
● shielded, max.
200 m
Analog value generation for the outputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max.
13 bit
● Conversion time (per channel)
420 µs; 420 µs in the ranges 1 to 5 V and 4 to 20 mA; 300 µs in all ranges
Settling time
● for resistive load
0.1 ms
● for capacitive load
3.5 ms
● for inductive load
0.5 ms
Errors/accuracies
Operational error limit in overall temperature range
● Voltage, relative to output range, (+/-)
0.5 %; +/-10 V, 0 to 10 V, 1 to 5 V
● Current, relative to output range, (+/-)
1 %; +/-20 mA, 4 to 20 mV
Basic error limit (operational limit at 25 °C)
● Voltage, relative to output range, (+/-)
0.5 %; +/-10 V, 0 to 10 V, 1 to 5 V
● Current, relative to output range, (+/-)
0.5 %; +/-20 mA, 0 to 20 mA
Potential separation
Potential separation analog outputs
● between the channels and backplane bus
Yes
Isolation
Isolation tested with
2120 V DC between bus and L+/M; 2120 V DC between bus and analog part; 500 V DC between bus and local ground; 707 V DC between analog part and L+/M; 2120 V DC between analog part and local ground; 2120 V DC between L+/M and local ground
Ambient conditions
Ambient temperature during operation
● min.
0 °C; = Tmin
● max.
60 °C; = Tmax
Ambient temperature during storage/transportation
● min.
-40 °C
● max.
70 °C
Extended ambient conditions
● relative to ambient temperature-atmospheric pressure-installation altitude
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
Relative humidity
— With condensation, tested in accordance with IEC 60068-2-38, max.
100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
— against biologically active substances / conformity with EN 60721-3-3
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
— against chemically active substances / conformity with EN 60721-3-3
Yes; Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
— against mechanically active substances / conformity with EN 60721-3-3
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!