Technická data
Název:
SIPLUS S7 Y-Koppler
Popis:
SIPLUS S7-400 Y-COUPLER FOR MEDIAL STRESS BASED ON 6ES7197-1LB00-0XA0
Technické informace:
General information | ||
Requirements for DP master system | ||
● Length of parameter assignment telegram | 244 byte | |
Supply voltage | ||
Design of the power supply | via bus module | |
permissible range, lower limit (DC) | 20.4 V | |
permissible range, upper limit (DC) | 28.8 V | |
Interfaces | ||
PROFIBUS DP | ||
Properties of the lower-level DP master system | ||
— Transmission rate, max. | 12 Mbit/s; 45.45 kbit/s to 12 Mbit/s | |
— Termination of lower-level DP master system | Active terminating resistor (Bus Terminator) | |
— Use of OLM/OBT | Yes | |
— Use of RS 485 repeaters, max. | 9 | |
— Number of DP slaves, max. | 31; 64 when using RS 485 repeaters or OLM/OBT | |
Protocols | ||
PROFIBUS DP | Yes | |
Interrupts/diagnostics/status information | ||
Status indicator | No | |
Alarms | No | |
Diagnostic functions | Yes | |
Potential separation | ||
to lower-level DP master system | Yes | |
Ambient conditions | ||
Ambient temperature during operation | ||
● min. | 0 °C; = Tmin | |
● max. | 60 °C; = Tmax | |
Ambient temperature during storage/transportation | ||
● min. | -40 °C | |
● max. | 70 °C | |
Extended ambient conditions | ||
● relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | |
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Dimensions | ||
Width | 40 mm | |
Height | 125 mm | |
Depth | 130 mm | |
Weights | ||
Weight, approx. | 200 g | |
last modified: | 02/01/2017 |